Cooler Door Specs
Door leaves to have aluminum extruded structure and to be metal clad with #24 gauge white galvanized steel front and back. Frame (casings and header) to be constructed of aircraft quality aluminum extrusions with white painted finish.
Door leaves to be filled with 4" of Jamifoam® non-CFC polyurethane insulation with an R value of 28 at 40oF. Frame to be insulated with polystyrene inserts.
Adjustable gasket at sides and head of frame and centering meeting edges to be polyester reinforced; door leaves to have sweep type sill gasket.
Hardware to have protective coating against corrosion. |
Freezer Door Specs Freezer door specs to be same as cooler door except for these substitutions and additions:
Provide Frostop® heater cables in top, sides, lead edges and bottom of door. Complete device to have UL LISTED components and to be assembled, ready for connection to 120 volt, 60 Hertz, single phase AC line.
Special Notes:
- Freezer Door is designed for installation in warm room with temperatures plus 33oF. and above. If door must be mounted in rooms with temperatures of +32oF. and below, contact factory.
- When cold room temperature is below -20oF. and/or the relative humidity is greater than 80% on the warm side, Frostop® heater cables should be added to the frame/gasket assembly.
- If the cold room temperature is below -40oF., or if the temperature difference exceeds 90oF., contact factory.
|